of equipment used in the specified system configuration. MTTR for this
system shall not exceed [30] [_____] minutes of on-site time for any one
element.
2.3.5
Alarms
Alarms shall include but not be limited to the following:
a.
Intrusion detection
b.
Tamper switches
c.
Fail-safe capability
d.
Line fault (for hardwire systems only) detection
e.
Power loss detection
2.3.5.1
Intrusion Detection
Include full range of interior point protection sensors, volumetric (space)
protection sensors, exterior fence sensors, and duress alarms. Duress
alarms shall be [annunciated to be clearly distinguishable from other
intrusion detection alarms] [silent at the reporting location and clearly
distinguishable from other intrusion detection alarms] at the central
reporting processor.
2.3.5.2
Tamper Switches
Enclosures, cabinets, housings, boxes, raceways, and fittings with hinged
doors or removable covers which contain circuits of the intrusion detection
system and associated power supplies shall be provided with cover having
corrosion-resistant tamper switches. Arrange tamper switches to initiate
an alarm signal when the door or cover is moved as little as 6 mm 1/4 inch
from the normally closed position. Mechanically mount tamper switches to
maximize defeat time when enclosure covers are opened or removed. Minimum
amount of time required to depress or defeat the tamper switch after
opening or removing the cover shall be one second. Enclosure and tamper
switch shall prevent direct line of sight to internal components and
prevent switch or circuit tampering. Conceal mounting hardware so switch
cannot be observed from enclosure exterior. Covers of junction boxes
provided to facilitate initial installation of the system need not be
provided with tamper switches if covers contain no splices or connections.
Tamper alarms shall be annunciated to be clearly distinguishable from
intrusion detection alarms. Tamper switches on doors which must be opened
to make normal maintenance adjustments to the system and to service power
supplies shall be the push/pull-set, automatic-reset type. Tamper switches
shall be:
a.
Inaccessible until switch is activated;
b.
Under electrical supervision at all times, irrespective of the
protection mode in which the circuit is operating;
c.
Spring-loaded and held in the closed position by the door, or
cover protected;
d.
Wired to break the circuit when the door or cover is disturbed;
and
SECTION 13703N
Page 19