h.
Connection of door frame to shield
i.
Clearances
1.4.6
HEMP Shielded Door
Submit certification indicating HEMP shielded door being provided has been
tested for compliance with MIL-STD-188-125. Submit test data supporting
these certifications.
1.5
DELIVERY, STORAGE, AND HANDLING
Package HEMP shielded door for shipment. HEMP shielded door shall be
shipped assembled with the door frame to hold the door and frame in
alignment. Packaging shall include physical, temperature, and moisture
protection, so that door is delivered to jobsite in an undamaged condition.
HEMP shielded door shall not be accepted at the jobsite with visible
damage. Provide special physical, temperature, and moisture protection
upon door arrival at jobsite; before, during, and after door installation
through completion of building construction. Provide protection
instructions from HEMP shielded door specialist (manufacturer) when special
protection is required after installation but before building completion.
Provide adequate protection prior to beneficial occupancy. Do not allow
materials to be exposed to extreme temperature and humidity. Ship the door
assembled with the door frame. Exercise great care when packing, shipping,
unpacking and installing the HEMP shielded door and frame assembly.
1.6
COORDINATION
Avoid unauthorized penetrations. Repair work damaged as a result of
unauthorized penetrations, discontinuities or other adverse changes to SA
of the system.
1.7
WARRANTY
**************************************************************************
NOTE: The warranty clause in this guide
specification may require Level I Contracting
Officer approval. Designer should consult the
appropriate Engineering Field Division/Activity for
guidance.
**************************************************************************
HEMP shielded door shall be warranted to provide the required SA, for a
period of [15] [_____] years. Parts and labor for operating mechanisms,
including the interlocking components, shall be warranted by the Contractor
for at least [3] [_____] years following the date of beneficial use. Any
part of these mechanisms or component(s) causing operating or attenuation
degradation of 5 dB or more during the warranty period shall be repaired or
replaced, including the required reinstallation and testing by the
Contractor. HEMP shielded door assemblies shall be suitable for repetitious
use. Adequate structural strength and permanent sealing is required to
meet the total specification, usage, and [15] [_____] year service life
requirements. Assemblies including doors, hardware, shielding devices,
sealing operating mechanisms, and other components shall function properly
through [10,000] [_____] cycles of use.