2.3.4
Threshold Alarm
Provide press-it-any-point ribbon switches for use with threshold to
enunciate alarm when pressure is applied to the threshold of HEMP shielded
door.
2.3.5
Hold Open Device
Provide each HEMP shielded door leaf with a hold open device permanently
attached to the door leaf.
2.3.6
Counting Device
Provide electric or electronic device for counting open, close cycles of
HEMP shielded door.
2.3.7
Door Stop
Provide door stop to prevent HEMP shielded door from hitting the wall.
2.4
EMERGENCY EXIT HEMP SHIELDED DOOR
Equip emergency exit HEMP shielded door with panic hardware. The force
required to latch and unlatch the emergency exit HEMP shielded door shall
meet Life Safety Code NFPA 101. Alterations or modifications in the field
to panic hardware are prohibited.
2.5
PAINTING
Paint HEMP shielded door in accordance with Section 09900 PAINTS AND
COATINGS with an environmentally acceptable, OSHA approved rust inhibiting
factory finish painted; provided damaged paint is touched-up. Do not paint
stainless steel surfaces and grounding contacts.
2.6
TOOLS
Furnish one full set of special tools that are required to maintain each
type of door provided under this contract and that are not typically
available from tool vendors. Furnish environmentally safe lubricants,
quantities to last for [3] [_____] years.
2.7
ELECTRIC CONNECTIVITY
Install sensors, alarms, interlocks and filters in accordance with HEMP
shielded door manufacturer's instructions.
2.8
MAINTENANCE SUPPLIES AND PROCEDURES
Deliver for each door maintenance supplies sufficient for a [3] [_____]
year period or [50,000] [_____] cycles, whichever is greater. Include the
activity and entry location for certifying that the maintenance was
undertaken. Provide a counting device to show the number of door open
close cycles. Prominently display maintenance instructions required to
maintain the door through the cycle count. Maintenance procedures shall be
such that the HEMP SA meets the requirements of MIL-STD-188-125.
SECTION 13095N
Page 14