1394 ports
n. Data/Fax Modem
o. Network Card: Integrated 10/100Base-T networking interface
p. Keyboard: QWERTY, 105 keys in ergonomic shape with 2 USB ports
q. Mouse: USB Optical Scrolling, two-button Mouse
2.2.2
Color Monitor
The monitor shall be sized as shown, but not less than 475 mm 19 inches,
viewable area with a minimum resolution of 1280 by 1024 pixels,
nonintegrated, and a maximum dot pitch of 0.24 mm. The video output card
shall support at least 256 colors at a resolution of 1280 by 1024 at a
minimum refresh rate of 70 Hz.
2.2.3
The laser printer shall meet the following requirements:
a.
Resolution: 1200 by 1200 dots per inch
b.
Printing Time: 16 pages per minute
c.
Data Buffer Size: 32 Megabytes
d.
Media Size: 216 X 279 mm 8.5 X 11 inches
e.
f.
Paper Cassette: 500 sheet capacity
2.2.4
A self contained UPS suitable for installation and operation at the server
shall be provided and sized to provide a minimum of 10 minutes of operation
of the server equipment. Equipment connected to the UPS shall not be
affected in any manner by a power outage of a duration less than the rated
capacity of the UPS. UPS shall be complete with all necessary power
supplies, transformers, batteries, and accessories and shall include visual
indication of normal power operation, UPS operation, abnormal operation and
visual and audible indication of low battery power. Provide USB connection
with software for automatic shutdown of data applications.
2.3
FM RADIO CONTROL APPLICATION SOFTWARE
The energy management software shall have the capability to create
customizable control strategies to be implemented by the owner. The system
shall also include, at a minimum, the following predefined control
strategies: direct load control, distributed generation monitoring and
control, capacitor bank control, voltage regulator control and thermostat
setback control. The system shall have two control modes, manual and
automatic. Manual mode shall allow the user to define when specific
strategies or groups go into and out of control. Automatic mode shall use
the predefined or customized triggers to implement the control strategies.
The system shall include, at a minimum, the following predefined control
triggers: time of day schedules, digital inputs, kW demand set-points, kVAR
setpoints, seasonal and temperature. The system shall provide web
interface capability to all energy data and reports.
2.4
**************************************************************************
NOTE: Edit the following to reflect site
conditions. Designer must specify if an energy
management software package will be provided or an
SECTION 16797A
Page 11