[_____] ice without failure. The antenna system shall be selected by the
Contractor to meet the requirements as determined from the topography.
2.8.1
Grounding Conductors
Antenna grounding conductors shall be minimum 32-strand, No. 8 AWG copper.
2.8.2
Ground Rods
Ground rods shall be as specified in Section 16370A ELECTRICAL DISTRIBUTION
SYSTEM, AERIAL.
2.8.3
Transmission Line
The transmission line between transmitter and antenna shall be 50 ohm
impedance, foam dielectric coaxial cable rated for the transmitter output
power. Minimum requirement shall be RG-8/U foam dielectric. For lengths
corrugated copper outer sheath type with either foam or air dielectric.
PART 3
EXECUTION
3.1
INSTALLATION
**************************************************************************
NOTE: Coordinate with appropriate electrical
sections required by the design.
**************************************************************************
System components and appurtenances shall be installed in accordance with
services, and adjustments required for a complete and operable radio
control system shall be provided and shall be fully integrated with the
UMCS. Grounding shall be in accordance with IEEE Std 142.
3.1.1
Software
The Contractor shall load all software required for a completely
operational one-way FM radio control. The Contractor shall adjust, tune,
debug, and commission all software and parameters for controlled systems to
assure proper operation in accordance with the specification.
3.1.2
Antenna
Tubular radiator elements shall be plugged to prevent wind vibration
fatigue. Vertical tubular elements shall have drain holes near the bottom.
Outside connectors shall be snug, filled with silicone grease, and
properly sealed with heat-shrink wrap suitable for ambient temperatures of
minus 30 to 60 degrees C minus 22 to 140 degrees F.
3.1.3
Interior Work
Interior electrical work shall be installed as specified in Section 16402
INTERIOR DISTRIBUTION SYSTEM and as shown.
SECTION 16797A