All other equipment shall be rated for continuous operation under the
ambient environmental temperature, pressure, humidity, and vibration
conditions specified or normally encountered for the installed location.
1.2.3
Electrical Requirements
**************************************************************************
power sources and UPS if required.
**************************************************************************
The equipment shall operate from an AC voltage source as shown, plus or
minus 10 percent, at a frequency of 60 Hz, plus or minus 2 percent. The
backup system transmission shall be connected to the uninterruptible power
supply (UPS) as specified and shown.
1.2.4
Power Line Surge Protection
Equipment connected to AC circuits shall be protected from power line
surges. Equipment shall meet the requirements of IEEE C62.41. Fuses shall
not be used for surge protection.
1.2.5
Communications Links Surge Protection
communications link. Cables and conductors which serve as communications
links shall have surge protection circuits installed at each end.
Protection shall be furnished at equipment and additional triple electrode
gas surge protectors rated for the application on each circuit shall be
installed within 1 meter 3 feet of the building cable entrance. Surge
protection shall meet the requirements of NFPA 780 guidelines and
specifications.
1.3
RADIO FREQUENCY COMMUNICATION EQUIPMENT (RFCE) SYSTEM REQUIREMENTS
The command transmitter and antenna installations shall be designed to
maintain minimum field strength of 30 microvolts/meter at any point in the
controlled area during transmission.
1.4
TECHNICAL DATA AND COMPUTER SOFTWARE
**************************************************************************
NOTE: The acquisition of technical data, data bases
and computer software items will be in accordance
with the Federal Acquisition Regulation (FAR) and
the Department of Defense Acquisition Regulation
Supplement (DFARS). Those regulations, as well as
the Army and Corps of Engineers implementations
thereof, should be consulted to ensure that a
delivery of critical items of technical data is not
inadvertently lost.
Specifically, the Rights in Technical Data and
Computer Software Clause, DFARS 52.227-7013, and the
Data Requirements Clause, DFARS 52.227-7031, as well
as any requisite software licensing agreements will
be made a part of the CONTRACT CLAUSES or SPECIAL
CONTRACT REQUIREMENTS of the contract. In addition,
the appropriate DD Form 1423 Contract Data
SECTION 16797A
Page 5