ELECTRONIC INDUSTRIES ALLIANCE (EIA)
EIA ANSI/EIA/TIA-232-F
(2002) Interface Between Data Terminal
Equipment and Data Circuit-Terminating
Equipment Employing Serial Binary Data
Interchange
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41
(1991; R 1995) Recommended Practice for
Surge Voltages in Low-Voltage AC Power
Circuits
IEEE Std 142
(1992) Recommended Practice for Grounding
of Industrial and Commercial Power Systems
- Green Book
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250
(2003) Enclosures for Electrical Equipment
(1000 Volts Maximum)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 780
Protection Systems
UNDERWRITERS LABORATORIES (UL)
UL 1585
(1998; Rev thru Feb 2004) UL Standard for
Fourth Edition
UL 512
1.2
SYSTEM DESCRIPTION
1.2.1
General
**************************************************************************
NOTE: Designer must show location of radio
frequency (RF) equipment to be controlled. Designer
must also show any Government furnished equipment
(GFE).
**************************************************************************
A complete one-way FM radio control system shall be provided. The system
shall consist of the energy management software and computer, command
generator, transmitter, communication links, antenna system, radio
switches, communication links surge protection, and power line surge
protection. [The system shall be compatible with the existing one-way FM
radio control equipment shown.] [The system shall be interfaced with the
UMCS as shown.]
1.2.2
Environmental Requirements
Equipment to be utilized indoors shall be rated for continuous operation
SECTION 16797A
Page 4