power sources.
**************************************************************************
The equipment shall operate from a voltage source as shown, plus or minus
10 percent, and 60 Hz, plus or minus 2 percent.
1.2.4
Power Line Surge Protection
Equipment connected to ac circuits shall be protected from power line
surges. Equipment shall meet the requirements of IEEE C62.41. Fuses shall
not be used for surge protection.
1.2.5
Communications Links Surge Protection
communications link. Cables and conductors which serve as communications
links shall have surge protection circuits installed at each end that meet
RUS Bull 345-50 requirements. Additional triple electrode gas surge
protectors meeting the requirements of RUS Bull 345-83 shall be provided on
each pair of conductors within 900 mm 3 feet of the building cable entrance.
1.2.6
Communications Links Overvoltage Protection
communications links. Cables and conductors which serve as communications
links shall have overvoltage protection for voltage up to 480 Vac rms, 60
Hz installed. Instrument fuses or fusible resistors are acceptable for
this application.
1.3
DELIVERY OF TECHNICAL DATA
**************************************************************************
NOTE: The acquisition of all technical data, data
bases and computer software items that are
identified herein will be accomplished strictly in
accordance with the Federal Acquisition Regulation
(FAR) and the Department of Defense Acquisition
Regulation Supplement (DFARS). Those regulations as
well as the Army and Corps of Engineers
implementations thereof should also be consulted to
ensure that a delivery of critical items of
technical data is not inadvertently lost.
Specifically, the Rights in Technical Data and
Computer Software Clause, DFARS 52.227-7013, and the
Data Requirements Clause, DFARS 52.227-7031, as well
as any requisite software licensing agreements will
be made a part of the CONTRACT CLAUSES or SPECIAL
CONTRACT REQUIREMENTS of the contract. In addition,
the appropriate DD Form 1423 Contract Data
Requirements List, will be filled out for each
distinct deliverable data item and made a part of
the contract. Where necessary, a DD Form 1664, Data
Item Description, shall be used to explain and more
fully identify the data items listed on the DD Form
1423.
It is to be noted that all of these clauses and
SECTION 16790A
Page 5