room along the corridor.
(2) Outside entries to patient care areas that are equipped with code
blue or infant code blue stations, zone lights are provided to direct code
response teams into the patient care area. These zone lights shall be
programmed to only indicate code calls. Once the code response team is
inside the patient care area, they will then follow the code call
indications on the zone lights within the area.
**************************************************************************
NOTE: Prepare and add Zone Light Activation
Matrices as noted below. Include the Matrices as
part of Schedules as indicated at the end of this
Section.
**************************************************************************
(3) The Zone Light Activation Matrices at the end of this Section
lists the identification (ID) number of all zone lights indicated on the
telecommunications plans, and relates these to the patient care rooms where
calls are originated that activate the zone lights.
c.
Call Routing - Master Stations
Master station features shall provide the attendant with the selectable
call routing defined below. This shall include the routing of voice
intercom between any master station and any audio call station.
(1) A default call routing scheme within each patient care area shall
be established for calls between each call originating station and the
master station(s) in a NC Subsystem. If there is more then one master
station in a NC Subsystem, then the default call routing to each master
station shall be user defined and approved by the Contracting Officer.
(2) Any call from any call originating station can be selectively
routed to, and answered from, any master station in any NC Subsystem
throughout the entire integrated NCAV System.
(3) Any one master station in any NC Subsystem shall be able to
handle any combination of calls, or all of the calls, from any call
originating station in any NC Subsystem.
(4) Any combination of master stations throughout all NC Subsystem
can be programmed to operate in a parallel mode. In this parallel mode, all
calls that would normally be routed to a master station will now be routed
to all master stations in the parallel mode at the same time. The parallel
mode can be either a default setting or an attendant selectable mode at any
master station.
(5) An attendant at any master station shall be able to perform a
selective call capture function whereby any call originating station that
has been default programmed for call routing to any other master station
shall be rerouted to the capturing master station. The attendant shall be
able to selectively capture single rooms, groups of rooms, or all the rooms
that have been default assigned to another master station. The rerouting
of calls from any room shall include all associated patient and caregiver
data that has been programmed for the room, including caregiver duty
assignments.
(6) Master stations that have relinquished reception of calls to
SECTION 16731A