2.3.6
Frangible Couplings and Adapters
MS 17814. Provide upper section of frangible coupling with one of the
following:
a.
Unthreaded for slip-fitter connections.
b.
60 mm 2 13/32 inch: 16N-1A modified thread for nut and
c.
53 mm 2 inch: 11 1/2-N.P.T. (tapered) with 5.5 mm 7/32-inch
nominal wall thickness to accept rigid conduit coupling.
[2.3.6.1
Frangible Couplings for Specialized Applications
Acceptable as approved.
]2.3.6.2
Electrical Metallic Tubing
UL 797. Provide where indicated for use with frangible couplings and
adapters.
2.4
WIRE AND CABLE
Do not provide or install wire and cable manufactured more than one year
before delivery to the job site. Conductors shall be copper.
2.4.1
Conductor Sizes
Conform to American Wire Gage (AWG).
2.4.2
Low Voltage Wire and Cable
**************************************************************************
NOTE: Type THW insulation can only be obtained in
large quantity. Use of this type insulation is not
recommended for small project.
**************************************************************************
[UL 854, Type USE, 600 volts for underground low voltage power cables.] [[
UL 83, Type [_____][THW][THWN]][UL 44, Type [XHHW][_____]] for secondary
series lighting circuits. Provide wire with "W" in the type designation in
wet or damp locations. ][As specified in Section 16302N UNDERGROUND
TRANSMISSION AND DISTRIBUTION.]
2.4.3
[Rated [5][_____] kV, [133 percent][_____] insulation level, with shield
and jacket conforming to [NEMA WC 7 for crosslinked polyethylene][ or ][
NEMA WC 8 for ethylene-propylene rubber] insulated cables. ][Provide as
specified in Section 16302N UNDERGROUND TRANSMISSION AND DISTRIBUTION.]
2.4.4
Wire and Cable for Airfield Lighting Systems
**************************************************************************
NOTE: FAA AC 150/5345-7 covers Type A (rubber),
Type B (ethylene-propylene), and Type C (crosslinked
polyethylene) cable. Each type has 600-volt and