2.12.1
Encapsulated Isolating Transformers
FAA AC 150/5345-47, Type (G) L-830 or MIL-T-27535. Provide each
transformer with rating as indicated. Insulation Level Primary voltage
rating 5000 volts RMS, Secondary 600 V RMS. Operating Temperature range
minus 55 degrees Celsius to plus 65 degrees Celsius. Resistant to UV
exposure and ozone. Suitable for areas contaminated with oils, aircraft
fuels, soil acids, alkalis, and deicing fluids. Compatible with FAA Style
2 and Style 9 connectors.
2.12.1.1
FAA E-2690. Encapsulated, submersible type with lifting handles and rating
of 1500 watts, 2400 volts, 20 amp primary, [6.6][20] amp secondary, [as
indicated,] single phase, 60 Hz. Primary and secondary leads shall conform
to FAA AC 150/5345-7, Type L-824.
[2.12.2
**************************************************************************
NOTE: Insert appropriate Section number and title
in the blank below using format per UFC 1-300-02.
**************************************************************************
As specified in [_____].
]2.13
LIGHT BASES
**************************************************************************
NOTE: Use Type L-867 bases for applications not
subject to aircraft or vehicle loading. Use Type
L-868 bases for applications subjected to aircraft
or vehicle loading. Use Type L-869 as a junction
box in all pavements.
**************************************************************************
FAA AC 150/5345-42 Type [L-867][L-868][L-869][ or ][FAA E-1315Type
[LB-1A][_____]]. Provide steel bases, Class 1, [Size [A][B][C][D] as
indicated] [or] as required to accommodate the fixture or device installed
thereon if diameter is not shown.
2.13.1
Accessories
Provide base plates, cover plates, and adapter plates to accommodate
various sizes of fixtures. Bolts shall be stainless steel.
2.14
SEALING FIXTURES AND WIRES IN DRILLED HOLES OR SAW KERFS
FAA AC 150/5370-10, Type P-606.
2.14.1
Sealant Type
FAA Type P-606 sealant for use in asphaltic concrete (AC) or Portland
cement concrete (PCC) pavement compatible with AC pavement and having a
minimum elongation of 50 percent. Formulations of Type P-606 which are
compatible with PCC pavement only are prohibited.
SECTION 16522N