Nominal voltage class.....................................[_____]
BIL.......................................................[_____]
Momentary asymmetrical current in the closed position.....[_____]
Momentary asymmetrical current in the bypass position.....[_____]
Continuous and interrupting current.......................[_____]
2.22.3
Miscellaneous
Standard accessories and components in accordance with IEEE C57.15shall be
provided. Single-phase units shall be provided with additional components
and accessories required by IEEE C57.15 for three-phase units.
2.23
ELECTRICAL TAPES
Tapes shall be UL listed for electrical insulation and other purposes in
wire and cable splices. Terminations, repairs and miscellaneous purposes,
electrical tapes shall comply with UL 510.
2.24
CALKING COMPOUND
Compound for sealing of conduit risers shall be of a puttylike consistency
workable with hands at temperatures as low as 2 degrees C 35 degrees F,
shall not slump at a temperature of 150 degrees C 300 degrees F, and shall
not harden materially when exposed to air. Compound shall readily calk or
adhere to clean surfaces of the materials with which it is designed to be
used. Compound shall have no injurious effects upon the workmen or upon
the materials.
2.25
NAMEPLATES
**************************************************************************
NOTE: Do not use this paragraph for Navy projects.
The Navy uses Section 16050, "Basic Electrical
Materials and Methods" which contains these
requirements.
**************************************************************************
2.25.1
General
Each major component shall have the manufacturer's name, address, type or
style, model or serial number, and catalog number on a nameplate securely
attached to the equipment. Equipment containing liquid-dielectrics shall
have the type of dielectric on the nameplate. Nameplates shall be made of
noncorrosive metal. As a minimum, nameplates shall be provided for
transformers, regulators, circuit breakers, capacitors, meters and switches.
2.26
SOURCE QUALITY CONTROL
**************************************************************************
NOTE: Use "reserves the right to" on all projects,
except those for SOUTHNAVFACENGCOM.
**************************************************************************
SECTION 16301N