For UPS installations within Seismic zones [1] [2] [3] [4], provide
equipment anchor to protect against seismic shock in accordance with
applicable local regulations.
3.1.8
Conduit Entries
Provide conduits using the available conduit areas shown on manufacturer's
installation drawings. Conduit entries shall not be made through the
front, side or rear panels of the UPS or [Maintenance Bypass Cabinets]
[System Control Cabinet].
[3.1.9
Battery Rack Assembly
**************************************************************************
NOTE: Choose this paragraph or the one below
entitled "Battery Cabinet".
**************************************************************************
Battery racks are shipped dismantled in separate rail, frame, and brace
packages. Ensure that necessary assembly hardware is included in the frame
packages. Installation of battery racks shall conform to the
manufacturer's instructions provided as Attachment B to this section.
][3.1.10
Battery Cabinet
Battery cabinets are factory assembled and are suitable for 25, 50 and 100
KVA UPS systems.
]3.1.11
Installation of battery shall conform to the manufacturer's instructions
provided in Attachment B.
**************************************************************************
NOTE: Appendix B provides information on the type
of battery used in the UPS application. This
information will include battery and racks data,
mounting information, charging instruction, etc. It
is the Contractors responsibility to familiarize
himself with this information prior to the start of
work.
**************************************************************************
3.1.11.1
Positioning Cells
Use lifting belt and spreader when lifting the cells with mechanical
equipment such as a crane or hoist. Install cells on racks in accordance
with manufacturer's instructions. Ensure each hydrometer tube is located
on aisle side of each cell.
3.1.11.2
Connecting Cells
Cleaning contact surfaces, application of no-oxide grease, and connection
of cells shall be in accordance with the manufacturer's instructions.
No-oxide grease is applied only on connection surfaces.
SECTION 16262N
Page 9