a.
[_____][One]-[_____] KVA - [_____] (Volts) UPS Systems.
Type:
[Non-Redundant] [Parallel Redundant].
b.
[_____][One]-[Maintenance Bypass Cabinets] [System Control
Cabinet(s)]
c.
[_____][One]-Remote Monitor Panels
d.
e.
[_____][One] Battery system(s) each consisting of [182] [192]
[210] [240] [_____] cells, inter-cell connecting hardware,
identification decals, and miscellaneous hardware. This does not
include tier-to-tier or rack-to-rack cables specified in paragraph
entitled "Inter-Rack and Inter-Tier Cables." The battery cells
are as follows:
Cell type:
[_____]
Cell dimensions:
[_____]
Cell weight (dry):
[_____]
Electrolyte per cell:
[_____]
f.
[_____](Each)-[_____] foot battery rack(s) [standard], [shock
protected], [seismic] type, each weighing [_____] kg [_____] lbs.
g.
[_____](Each) battery cabinets each weighing [_____] kg [_____] lbs.
h.
[_____](Each) 56.83 liters 15 gallon DOT 37P-2U poly-lined steel
drums of electrolyte. Each drum of electrolyte weighs
approximately 77 kg 170 pounds.
PART 3
EXECUTION
3.1
INSTALLATION
**************************************************************************
NOTE: Manufacturer's installation drawing, wiring
diagrams, battery, racks and cabinets' information
shall be obtained from NFESC ECDet, Code 65.
Appropriate information and data will form an
integral part of these specifications.
**************************************************************************
Conform to the requirements for electrical equipment installations
specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM, to the
requirements specified herein, and in strict accordance with NFPA 70, and
manufacturer's installation drawings and wiring diagrams to include overall
dimensions, front view, and sectional view, typical installation and module
arrangement, and ventilation and exhaust system. During and after
installation, until the system is accepted by the Contracting Officer,
Contractor shall protect UPS equipment, including batteries, from moisture,
dust, and contamination. Upon completion of the UPS system installation,
Contracting Officer and UPS manufacturer's technical representative will
SECTION 16262N
Page 7