equipment of the respective rating and type.
No substitute will
be accepted for the "Check Test".
SD-10 Operation and Maintenance Data
Manufacturer's Data and Instructions [_____]
[Six] [_____] copies of printed and bound instructions manual
for the proper installation, erection, inspection, and maintenance
of the machines furnished under this contract shall be supplied to
the Contracting Officer not later than the date the equipment is
shipped from the manufacturer's plant. Manuals shall include
complete installation, maintenance, and service instructions for
water requirements), and other accessories. The instructions
shall include a cross-sectional drawing indicating the major
component parts of the motor and procedure for disassembly. The
description in the manual for the motor shall be coordinated with
the installation erection instructions specified in Section 15131A
VERTICAL PUMPS, AXIAL-FLOW AND MIXED-FLOW IMPELLER-TYPE for the
pump and integrated with same for a complete motor and pump
assembly.
1.3
GENERAL REQUIREMENTS
1.3.1
The equipment provided under these specifications will be subjected to
severe moisture conditions and shall be designed to render it resistant to
corrosion from such exposure. The general requirements to be followed to
mitigate corrosion are specified below. Any additional special treatment
under the respective item. However, other corrosion-resisting treatments
that are the equivalent of those specified herein may, with the approval of
the Contracting Officer, be used.
1.3.1.1
Fastenings and Fittings
Where practicable, all screws, bolts, nuts, pins, studs, springs, washers,
and other similar fittings shall be of corrosion-resisting material or
shall be treated in an approved manner to render them resistant to
corrosion.
1.3.1.2
Corrosion-Resisting Materials
Corrosion-resisting steel, copper, brass, bronze, copper-nickel, and
nickel-copper alloys are acceptable corrosion-resisting materials.
1.3.1.3
Corrosion-Resisting Treatments
Hot-dip galvanizing shall be in accordance with ASTM A 123/A 123M or ASTM A
153/A 153M as applicable. Other corrosion-resisting treatments may be used
if approved by the Contracting Officer.
1.3.1.4
Frames
Motor frames, end bells, covers, conduit boxes, and any other parts, if of
steel, and if they will be coated during the process of insulating the
windings, shall be cleaned of rust, grease, millscale, and dirt, and then
SECTION 16222A
Page 9