Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Motors[; G][; G, [_____]]
[Six] [_____] copies of equipment foundation dimensions; outline
drawings for motor and rotor set-down fixture and jacking
provisions with weights, nameplate data, and details showing
method of mounting and anchoring the motor. Contracting Officer's
approval shall be obtained in writing prior to the commencement of
manufacture of motors.
SD-03 Product Data
Insulated Windings[; G][; G, [_____]]
A detailed description of and specification for the
manufacturing process, the materials and the insulating compound
used in insulating the windings shall be submitted to the
Contracting Officer for approval before manufacture of the motors
is commenced. If, in the opinion of the Contracting Officer, the
insulation proposed is not of the quality specified and if the
methods of manufacture are not considered to be in accordance with
best modern practice, the motors will not be accepted.
Witness Test[; G][; G, [_____]]
[Six] [_____] copies of motor design (characteristic) curves or
tabulated data indicating the efficiency, current, and kilowatt
input at rated voltage and 110 and 90 percent rated voltage, all
plotted or tabulated against torque or percent load as abscissas.
Where values are given in percentages all base values will be
indicated.
**************************************************************************
NOTE: See additional Note L. Use final sentence
only when the pump and motor are furnished under the
same procurement.
**************************************************************************
[Six] [_____] copies of the motor torque curves shall be plotted
for the following values of voltage at the motor terminals:
[rated and 90 percent of rated voltage] [the output of a
closed-transition autotransformer type reduced-voltage starter
supplied at rated and 90 percent of rated motor voltage and
connected on its [80] [65] percent tap]. [The pump torque curve
shall be plotted for starting, accelerating, and synchronizing
demonstrate that the motor will pull into synchronism under all of
the foregoing conditions.]
Motors[; G][; G, [_____]]
SECTION 16222A
Page 7