For Cooling Tower:
[_____]
Checklist Item
Q
M
E
T
C
D
O
U
Installation
a.
Cooling tower in place.
___ ___
X
___ ___ ___ ___ ___
b.
Cooling tower piped.
___ ___
X
X
___ ___ ___ ___
c.
Cooling tower fan drive adjusted.
___ ___ ___ ___
X
___ ___ ___
d.
Cooling tower makeup water supply piped. ___ ___
X
X
___ ___ ___ ___
e.
Verify makeup control valve shutoff.
___ ___
X
___
X
___ ___ ___
f.
Fan lubricated and blade pitch adjusted. ___ ___
X
___
X
___ ___ ___
g.
Manufacturer's required maintenance/
operational clearance provided.
___ ___
X
X
X
___ ___ ___
Electrical
a.
Power available to tower disconnect.
___ ___ ___
X
___ ___ ___ ___
b.
Power available to electric sump heater
and heater functional.
___ ___ ___
X
___ ___ ___ ___
c.
___ ___ ___
X
___ ___ ___ ___
d.
Motor and fan rotation checked.
___ ___ ___
X
___ ___ ___ ___
e.
Verify that power disconnect is located
within sight of the unit's controls.
___ ___ ___
X
___ ___ ___ ___
Piping
a.
Tower basin is clean and filled.
___ ___
X
X
X
___ ___ ___
b.
___ ___
X
X
X
___ ___ ___
c.
Water balance with design flow verified. ___ ___
X
___
X
___ ___ ___
d.
Water distribution headers balanced.
___ ___
X
___
X
___ ___ ___
SECTION 15995A
Page 19