before and during installation as recommended by the manufacturer. Replace
damaged or defective items free of charge to the Government. Describe
sectional shipments in proposal, otherwise it shall be understood that
equipment shall not require field assembly. The manufacturer shall pay
field assembly costs of sections, accessories, or appurtenances not listed
in the proposal as requiring field assembly.
1.5
DESIGN CRITERIA
1.5.1
Obtain approval of dust collector model tests prior drawing submittal.
Submit drawings for dust collector system components, dust collector system
indicate kind, size, design, arrangement, assembly, breakdown for shipment,
and weight. Include locations for external connections, controls, remote
control panels, anchorages, and supports. Indicate dimensions for
installation and correlation with other materials and equipment. Include
foundation and loading information.
[1.5.2
Boiler Data
**************************************************************************
NOTE: Select this paragraph or the paragraph below
entitled "Incinerator Data."
**************************************************************************
**************************************************************************
NOTE: Insert appropriate Section number and title
in the blanks below using format per UFC 1-300-02.
**************************************************************************
Design baghouse(s) for operation with [manually] [automatically] controlled
[boiler(s) specified in [_____]] [boiler(s) manufactured by [_____], Type
[_____], Model Number [_____]]. The boiler is a [new] [existing]
[pulverized coal fired boiler] [[_____] grate spreader stoker fired boiler]
[[_____] retort underfeed stoker fired boiler] rated [_____] kg/s lbs/hr
steam at [_____] kPa psi. Boiler gross heat input is expected to be [_____]
kW MBtu/hr and boiler steam output is expected to be between [[_____] and
[_____]] kg/s lb/hr. Boiler shall burn coal meeting the following
criteria. The standby fuel is [_____].
a.
Proximate analysis, as received, percent by weight:
Range
Moisture
[_____]
Ash
[_____]
Volatile matter
[_____]
Fixed carbon
[_____]
Total
100.00
Sulfur
[_____]
[_____]
b.
Ultimate analysis, as received, percent by weight:
Range
Moisture
[_____]
SECTION 15863N
Page 13