h.
Penthouse Roof: The walking surface on top of the penthouse; that
is, the raised pattern plate that covers the top of the penthouse
casing insulation.
i.
Plate Spacing: Center to center spacing of the grounded
collecting electrode surfaces.
1.3
DESCRIPTION
**************************************************************************
NOTE:
1. If fly ash conditioning or removal prior to the
precipitator is included in the design, the system
should be described.
2. If it is anticipated that the efficiency of the
precipitator will be increased by the addition of
field(s) in the future, this should be described.
3. If it is desired that the inlet and outlet
breeching be furnished and/or designed by the
collector manufacturer, it should be described.
4. Specify the ESP location and breeching tie
points.
**************************************************************************
Provide electrostatic precipitator(s) of the rigid frame type designed in
accordance with ICAC EP-1, ICAC EP-4, ICAC EP-5, ICAC EP-6, ICAC EP-7, and
ICAC EP-8 to remove fly ash from flue gas produced by a [pulverized
coal-fired boiler] [spreader stoker-fired boiler] [underfeed stoker-fired
boiler] [refuse-fired waste disposal incinerator]. Provide precipitator(s)
suitable for [indoor] [outdoor] installation. Locate the precipitator(s)
in the flue gas system between the [_____] and the [_____].
1.3.1
Drawings shall indicate the kind, size, arrangement, weight of each
component, and breakdown for shipment; the external connections, location
of local controls, remote control panels, anchorages, and supports
required; the dimensions needed for installation and correlation with other
materials and equipment; seismic structural calculations; and foundation
and loading information. Supply drawings for each component showing design
and assembly. Provide schematics of all electrical and pneumatic circuits
used. Submission shall include, but shall not be limited to the following
details:
a.
b.
High voltage switches and disconnects.
c.
d.
e.
Ground lugs.
f.
Protection against electrolysis.
SECTION 15862N