UFGS-15862N (September 1999)
------------------------------
Preparing Activity: NAVFAC
Replacing without revision
NFGS of same number and date
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated 23 June 2005
**************************************************************************
SECTION 15862N
ELECTROSTATIC DUST COLLECTOR OF FLUE GAS PARTICULATES
09/99
**************************************************************************
NOTE: This guide specification covers the
requirements for furnishing, installing, adjusting,
and testing of electrostatic precipitator(s).
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
**************************************************************************
NOTE: The precipitator(s) is intended to be used
for flue gas particulate removal and collection
associated with coal-fired boilers and refuse-fired
waste disposal incinerators. Coal-fired boilers
applicable to this specification are those designed
with capacities ranging between 3.78 and 31.5
kilogram of steam per second 30,000 and 250,000
pounds of steam per hour. The incinerators
applicable to this specification are those designed
for burning municipal-type waste having firing
capacities between 454 kilogram per hour 1,000
pounds per hour and 182 Mg 200 tons per day. For
engineering and design assistance on precipitators
applied close to or outside these capacities,
contact:
Commanding Officer (ESC Code 433)
NAVFAC Engineering Service Center
560 Center Drive
Port Hueneme, CA 93043-4340
SECTION 15862N