NEMA ICS 6
(1993; R 2001) Industrial Control and
Systems: Enclosures
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70
(2005) National Electrical Code
SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
(SMACNA)
SMACNA Arch. Manual
(2003, 6th Ed) Architectural Sheet Metal
Manual
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC PS 12.01
(2002) One-Coat Zinc-Rich Painting System
SSPC SP 1
(1982; R 2000) Solvent Cleaning
SSPC SP 6
(2000) Commercial Blast Cleaning
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 60
Standards of Performance for New
Stationary Sources
1.2
DEFINITIONS
Electrostatic precipitator terminology shall be in accordance with ICAC EP-1
except for the following:
a.
Aspect Ratio: Effective treatment length divided by effective
collection plate height.
b.
Collection Surface Area: Area of vertical grounded plates
parallel to the gas flow. The area of components in walkways,
hoppers, discharge electrical surfaces, inlet plenums, and outlet
plenums shall be excluded. Exclude area of plates above or below
the uniform gas flow.
c.
Effective Collection Plate Height: Vertical height of the
grounded collection plate in contact with the flue gas.
d.
Effective Treatment Length: Horizontal length of the grounded
collection plates parallel to the gas flow in a single passage in
the direction of gas flow. Exclude walkways, inlet plenums, and
outlet plenums.
e.
Specific Collection Area: Total grounded collection surface area,
in square meter feet, divided by maximum gas flow rate.
f.
Rigid Frame Type: Typical design in which the discharge
electrodes are fastened in a support frame of welded horizontal
and vertical masts suspended from four support insulators.
g.
Hot Roof: Top section of the precipitator casing between the
penthouse and the gas stream.
SECTION 15862N
Page 7