[multiple stages][ or ][Silicon Controlled Rectifier (SCR).] Provide UL or
ETL listed safety switches to protect system from overheating.]
2.1.6
Humidifier
Humidifier section shall include liquid-level control, emergency overflow
and automatic water supply system factory pre-piped for final connection.
Provide stainless steel evaporator pan with water high level and low level
alarms. Arrange system to be cleanable and serviceable.
[Provide infrared type humidifier, including high intensity quartz lamps
mounted above and out of water supply.]
[Provide low-watts density electric heater immersion type humidifier.
Provide entire assembly and removable pan of stainless steel construction.
Protect elements with high temperature limit cutout.]
[Provide steam generator type humidifier. Provide steam generator
humidifier cutout. Controls shall include steam generation, and flush
cycle. Furnish two extra cannisters.]
2.1.7
Refrigeration System
Provide compressor[s] complete with vibration isolation, suction and
discharge service valves, high and low pressure safety switches, and
built-in overload protection.
Provide refrigeration circuits including
hot gas mufflers, liquid-line filter-drier, refrigerant sight glass and
moisture indicator, externally equalized expansion valve, and liquid-line
solenoid valve factory connected with refrigeration copper tubing.
[Crankcase heaters are required.] [Provide hot gas bypass.]
[2.1.7.1
Compressors
**************************************************************************
NOTE: The purpose of the paragraph below is to
prevent the acquisition of a refrigerant compressor
design that is inferior from an energy efficiency or
control standpoint. Delete this paragraph if there
users or inferior contols at a given capacity.
However, if such an acquisition is probable, use the
selections below to prohibit the acquisition of
inferior designs.
**************************************************************************
Provide [single] or [dual], [hermetic] or [semi-hermetic] or [scroll]
compressors. [If dual compressors are provided, the refrigeration system
shall be equipped with two independent refrigeration circuits.] [Dual
semi-hermetic compressors shall be provided complete with unloading system.]
][2.1.7.2
Refrigerant Tubing
Field-installed refrigerant tubing for split systems shall be ASTM B 280,
cleaned, dehydrated, and sealed. Further, provide ASME B16.22 solder joint
refrigerant fittings and adapters with silver brazing alloy solder and
silver brazing alloy flux. During brazing operations bleed a small amount
of dry oil-free nitrogen continuously through the refrigerant tubing. If
required for connections to equipment, provide ASME B16.26 flared fittings.