2.2.1.2
Uninsulated Interior Surfaces and Exterior Surfaces
Polyelastomer resin: 3 coats, 0.100 to 0.150 mm (4 to 6 mils)
minimum total dry film thickness.
2.2.1.3
Insulated Interior Surfaces
Vinyl: 0.050 to 0.250 mm (2 to 10 mils) minimum dry film
thickness
2.2.2
Phenolic Finish Coating System
Provide a resin base thermosetting phenolic finish.
2.2.2.1
a.
Apply phenolic finish to the entire coil. Provide a minimum
of two coats. Total minimum dry film thickness shall be
0.075 mm (3 mils).
b.
In lieu of coating, provide coil of copper tubes and copper fins
2.2.2.2
Uninsulated Interior Surfaces and Exterior Surfaces
Amine cured epoxy phenolic finish:
0.150 to 0.175 mm (6 to 7
mils) minimum total dry film thickness.
2.2.2.3
Insulated Interior Surfaces
Polyester or Vinyl Ester finish:
0.050 to 0.250 mm (2 to 10
mils) minimum dry film thickness.
]2.3
ELECTRICAL
2.3.1
Electrical Motors, Controllers, Contactors, and Disconnects
Furnish with respective pieces of equipment. Motors, controllers,
contactors, and disconnects shall conform to Section 16402 INTERIOR
DISTRIBUTION SYSTEM, as modified and supplemented by this section. Provide
Provide controllers and contactors with maximum of 120-volt control
circuits, and auxiliary contacts for use with controls furnished. When
motors and equipment furnished are larger than sizes indicated, the cost of
providing additional electrical service and related work shall be included
under this section.
2.3.2
Electrical Control Wiring
[Provide control wiring under Section 15901N SPACE TEMERATURE CONTROL
SYSTEMS.] [Provide control wiring under Section 15910N DIRECT DIGITAL
CONTROL SYSTEMS.] [Provide control wiring under this section in accordance
with NFPA 70 and Section 16402 INTERIOR DISTRIBUTION SYSTEM.] Provide
Space temperature control system drawings which include point-to-point
2.4
[HVAC WATER PIPING] [AND] [METAL DUCTWORK]
**************************************************************************
NOTE: LANTNAVFACENGCOM Projects should use
SECTION 15702N
Page 15