be permitted.
PART 2
PRODUCTS
2.1
COMPUTER ROOM AIR CONDITIONING UNITS (CRACU)
**************************************************************************
NOTE: The indoor components of CRACU are inherently
noisy. In noise sensitive areas, designers should
take steps to attenuate CRACU generated sound.
Determine the maximum acceptable sound level limit
for the application in NC level or dbA and add the
limit to the CRACU equipment schedule. This sound
level compliance may be verified by the CRACU
factory and field tests.
**************************************************************************
**************************************************************************
NOTE: Designers should locate the floor registers
in a raised floor system as far from the CRACU as
possible to reduce direct sound transmission from
the unit to the conditioned space.
**************************************************************************
**************************************************************************
NOTE: Designers should indicate the mandatory
routing of piping around the floor stand of a
downflow CRACU in their piping plan view and piping
details. Ensure, by dimensioning of piping details,
that no piping interferes with the air flow
performance of the CRACU.
**************************************************************************
ASHRAE 15. Provide self-contained units, designed, [and] factory
assembled[, and factory tested]. Unit shall be listed in UL Elec Equip Dir
or ETL DLPfor computer room application. Unit shall include room cabinet
and frame, [floor stand, ]fan section, filter section, cooling coil, reheat
coil, humidifier, [compressors], [condensers], controls, and,
interconnecting piping internal to the CRACU.
2.1.1
Cabinet and Frame
2.1.1.1
Unit Cabinet
Unit frame shall be minimum 14 gage 2.0 millimeter welded steel tubes or
steel angles and shall be mill-galvanized or coated with an epoxy finish,
or an approved manufacturer's standard finish, if equivalent.
Exterior panels shall be furniture grade steel sheet, minimum of 20 gage
1.0 mm, mill-galvanized or coated with a corrosion-inhibiting epoxy finish,
or an approved equivalent finish. Mill galvanized sheet metal shall be
coated with not less than 1.25 ounces of zinc per square foot 380 gram of
zinc per square meter of two-sided surface. Mill rolled structural steel
shall be hot-dip galvanized or primed and painted. Cut edges, burns and
scratches in hot-dip galvanized surfaces shall be coated with galvanizing
repair coating.
Provide removable panel for access to controls without interrupting
airflow. Panels shall be gasketed to prevent air leakage under system
SECTION 15702N
Page 7