follow the format of the required testing standard for both the
Chiller Performance Tests and the Chiller Sound Tests. Test
report shall include certified calibration report of all test
that all test instrumentation has been calibrated within 6 months
certification that all instrumentation complies with requirements
of the test standard. Test report shall be submitted [1] [_____]
week after completion of the factory test.
System Performance Tests
[Six] [_____] copies of the report shall be provided in bound
216 x 279 (8 1/2 x 11 inch) 8 1/2 x 11 inch booklets.
SD-07 Certificates
Refrigeration System
Where the system, components, or equipment are specified to
comply with requirements of AGA, NFPA, ARI, ASHRAE, ASME, or UL,
[1] [_____] copy of proof of such compliance shall be provided.
The label or listing of the specified agency shall be acceptable
evidence. In lieu of the label or listing, a written certificate
from an approved, nationally recognized testing organization
equipped to perform such services, stating that the items have
been tested and conform to the requirements and testing methods of
the specified agency may be submitted. When performance
requirements of this project's drawings and specifications vary
from standard ARI rating conditions, computer printouts, catalog,
or other application data certified by ARI or a nationally
recognized laboratory as described above shall be included. If
ARI does not have a current certification program that encompasses
such application data, the manufacturer may self certify that his
application data complies with project performance requirements in
accordance with the specified test standards.
Service Organization
A certified list of qualified permanent service organizations
for support of the equipment which includes their addresses and
qualifications. The service organizations shall be reasonably
convenient to the equipment installation and be able to render
satisfactory service to the equipment on a regular and emergency
basis during the warranty period of the contract.
SD-10 Operation and Maintenance Data
[Six] [_____] complete copies of an operation manual in bound
216 x 279 (81/2 x 11 inch) 8 1/2 x 11 inch booklets listing
step-by-step procedures required for system startup, operation,
abnormal shutdown, emergency shutdown, and normal shutdown at
least [4] [_____] weeks prior to the first training course. The
booklets shall include the manufacturer's name, model number, and
parts list. The manuals shall include the manufacturer's name,
model number, service manual, and a brief description of all
equipment and their basic operating features. [Six] [_____]
SECTION 15620A