procedures, methods of checking the system for normal safe
operation, and procedures for safely starting and stopping the
system shall be prepared in typed form, framed as specified above
for the wiring and control diagrams, and posted beside the
diagrams. The framed instructions shall be posted before
acceptance testing of the systems.
Tests
Test procedure, as specified.
Welding Qualifications
A copy of qualified welding procedures and a list of names and
Field Training
Proposed schedule for field training, at least 2 weeks prior to
SD-06 Test Reports
Tests
Test reports shall be submitted in booklet form showing all
field tests performed to adjust each component and all field tests
performed to prove compliance with the specified performance
criteria, upon completion and testing of the installed system.
Each test report shall indicate the final position of controls.
The action settings for all automatic controls in the form of a
typed, tabulated list indicating the type of control, location
setting, and function shall be included. A written statement from
the manufacturer's representative certifying that combustion
control equipment has been properly installed and is in proper
operating condition, upon completion of the installation.
SD-10 Operation and Maintenance Data
Operating and Maintenance Instructions
step-by-step procedures required for system startup, operation,
and shutdown. The instructions shall include the manufacturer's
name, model number, service manual, parts list, and brief
description of all equipment and their basic operating features.
Maintenance instructions, prior to the field training course.
[Six] [_____] complete copies of maintenance instructions listing
routine maintenance procedures, possible breakdowns and repairs,
and troubleshooting guides. The instructions shall include piping
layout, equipment layout, and simplified wiring and control
diagrams of the system as installed.
1.3
GENERAL REQUIREMENTS
1.3.1
Standard Products
Material and equipment shall be the standard products of a manufacturer
SECTION 15555A