Performance data at minimum, 25 percent, 50 percent, 75 percent,
and 100 percent load
SD-06 Test Reports
Boiler system start-up tests
Submit test reports in accordance with section entitled "Field
Quality Control." Submit a detailed written record of the
start-up performance, including burner setting data over the
entire load range, before the Contractor's and sub-contractor's
test personnel leave the site.
SD-07 Certificates
Report of prior installations
Qualifications of engineer
Start-up plan
Start-up certification
Boilers
Submit evidence that boilers meet requirements of standards
specified. Include with the certificate of compliance acceptable
evidence that standards are met. Acceptable evidence will be the
official UL listing mark prescribed in the UL gas and oil
equipment list for oil-fired, gas-fired, or gas and oil-fired
boiler assemblies, as applicable plus the appropriate official
ASME symbol stamp. In lieu of the above certification, acceptable
evidence will be a test report from an independent testing
laboratory, indicating that the boilers and accessories have been
inspected and tested and meet requirements of the applicable
standards specified.
SD-10 Operation and Maintenance Data
Boilers, Data Package 4
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
1.5
QUALITY ASSURANCE
1.5.1
Report of Prior Installations
Boilers shall be shipped to the site of installation as [a] [an]
[completely assembled packaged boiler-burner unit] [unassembled package. A
competent installation engineer or technician as stated in paragraph
entitled "Qaulifications of Engineer" shall assemble an unassembled
boiler-burner package in strict accordance with the manufacturer's
instructions. ] Boilers and feedwater equipment installed shall be of
proven design which has been tested, successfully installed, and operated
in commercial or industrial installations. Submit a certified written
report from the boiler and feedwater equipment manufacturer indicating date
of installation, type, model, capacity, and address location of installed
SECTION 15516N
Page 8