o.
Seismic zone:
[_____].
1.3.1.5
Vertical Fuel Oil Storage Tanks
Design the tank to resist the following loads and forces:
Wind:
[_____] Pa pounds per square foot
Seismic zone:
[_____]
Roof live load:
[_____] kg/m2 pounds per square foot
Density of liquid:
[_____] kg/m3 pounds per cubic foot.
Allow the following combinations of loads, with corresponding percentages
of basic stresses to be used in design:
Percent of
Load Combination
Basic Stress
Dead load + live load
100
Dead load + live load + wind load
133
Dead load + live load + seismic load
133
1.3.1.6
Fuel Oil Pump and Heater Set
**************************************************************************
NOTE: Tabulated pump data is included in the
specifications but it is preferred that such
information be shown on the drawings instead.
**************************************************************************
a.
Pump/Heater Set
(1)
Capacity each pump and each steam heater:
[_____] L/s gpm
(2)
Suction lift:
[_____] kPa ft of water
(3) Discharge pressure at outlet of heater:
[_____] kPa (gage)
psig
(4)
Maximum pump speed:
1750 rpm
(5)
Specific gravity range:
[.92 to .99] [_____to_____]
(6)
Viscosity at BHP selection point:
5000 ssu
(7)
Viscosity range:
[500 to 5000] ssu [_____to_____] ssu
(8)
Oil temperature at inlet of heater:
[_____] degrees C F
(9)
Oil temperature at outlet of heater:
[_____] degrees C F
(10) Maximum oil pressure drop through heater:
[_____] kPa psi
Steam
(12) Steam pressure available:
[_____] kPa (gage) psig
SECTION 15511N
Page 17