submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Air compressor system
SD-03 Product Data
**************************************************************************
NOTE: Include carbon monoxide monitor in systems
which are used for breathing air per DM 3.5, Section
3.
**************************************************************************
Air compressor
Line silencer
Air flow rate and pressure recorder
[
Carbon monoxide monitor]
Filter housing
Submit manufacturer's catalog data for compressor and auxiliary
equipment in the format provided in API Std 619, Appendix A. For
system, and control valves. Submit air compressor, intercooler,
aftercooler, and bypass cooler performance curves at specified
overall physical features dimensions, ratings, service
requirements, efficiency, and weight of equipment.
SD-06 Test Reports
Air compressor performance tests
Sound level tests
Obtain approval prior to shipping compressor.
Government shall have the option to observe test procedures and
vendor will provide two (2) copies of test results and two (2)
Air compressor performance tests
Sound level and run-in tests
Air compressor system test
SECTION 15215N
Page 8