Submit the extinguishing system manufacturer's installation
manual.
SD-10 Operation and Maintenance Data
Fire extinguishing system, Data Package 3; G
System as-built drawings, Data Package 3; G
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
Sign legends; G
1.4
ELECTRICAL WORK
Associated with this section shall be provided under Section 16402 INTERIOR
DISTRIBUTION SYSTEM, except for control [and fire alarm] wiring. [Fire
alarm system is specified in Section 13852N INTERIOR FIRE ALARM SYSTEM.]
Provide control [and fire alarm] wiring [, including connections to fire
alarm systems,] under this section in accordance with NFPA 70. Provide
wiring in rigid metal conduit or intermediate metal conduit, except
electrical metallic tubing conduit may be provided in dry locations not
enclosed in concrete or where not subject to mechanical damage.
1.5
QUALITY ASSURANCE
1.5.1
Qualifications of Installer
Prior to installation, submit data showing that the Contractor has
successfully installed systems of the same type and design as specified
herein, or that the Contractor has a firm contractual agreement with a
subcontractor having such required experience. The data shall include the
names and locations of at least two installations where the Contractor, or
the subcontractor referred to above, has installed such systems. Indicate
type and design of each system and certify that each system has performed
satisfactorily in the manner intended for not less than 18 months.
Qualifications of System Technician: Installation drawings, shop drawing
and as-built drawings shall be prepared, by or under the supervision of, an
individual who is experienced with the types of works specified herein, and
is currently certified by the National Institute for Certification in
Engineering Technologies (NICET) as an engineering technician with minimum
Level-III certification in Special Hazard System program. Contractor shall
submit data for approval showing the name and certification of all involved
individuals with such qualifications at or prior to submittal of drawings.
PART 2
PRODUCTS
2.1
PREENGINEERED WET CHEMICAL FIRE EXTINGUISHING SYSTEMS
**************************************************************************
NOTE: If the piping between hood and storage
canisters is mounted
against....
specify
SECTION 13971N
Page 6