Backflow Preventers; G
Pressure Switch; G
Annotate descriptive data to show the specific model, type, and
size of each item.
SD-05 Design Data
**************************************************************************
NOTE: When a sprinkler system is designed using the
pipe schedule method, delete the paragraph entitled
"SD-05 Design Data."
**************************************************************************
Sprinkler system design; G
[
Submit computer program generated hydraulic calculations to
Calculations generated by computer program shall include the name,
address, and telephone number of the software manufacturer.]
SD-06 Test Reports
Preliminary tests on piping system; G
SD-07 Certificates
Qualifications of installer; G
SD-10 Operation and Maintenance Data
Dry pipe valves, Data Package 3; G
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
As-built drawings of each system; G
1.5
QUALITY ASSURANCE
1.5.1
Qualifications of Installer
Prior to installation, submit data showing that the Contractor has
successfully installed systems of the same type and design as specified
herein, or that Contractor has a firm contractual agreement with a
subcontractor having such required experience. Data shall include names
and locations of at least two installations where the Contractor, or the
subcontractor referred to above, has installed such systems. Indicate type
and design of each system and certify that each system has performed
satisfactorily in the manner intended for not less than 18 months.
SECTION 13935N
Page 9