fire department inlet connection, pressure or flow
switch, fused disconnect switch, and associated
2. Location where each sprinkler system begins
including connection to water distribution system
piping.
3. Location of sprinkler system control valves,
post indicator valves, or wall indicator valves.
4. Area of sprinkler system coverage when system is
protecting partial areas.
5. Details of anchoring piping, including pipe
clamps and tie rods, or mechanical retainer glands.
6. Indicate existing sprinkler piping layout and
sprinkler heads on project drawings only if existing
sprinkler system is being modified and such layout
is necessary for clarity.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
AMERICAN WATER WORKS ASSOCIATION(AWWA)
AWWA C651
(1999) Disinfecting Water Mains
ASME INTERNATIONAL (ASME)
ASME A17.1
(2004) Handbook on Safety Code for
FM GLOBAL (FM)
FM P7825
(2003) Approval Guide
FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH
(FCCCHR)
FCCCHR List
(continuously updated) List of Approved
Backflow Prevention Assemblies