MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-58
(2002) Pipe Hangers and Supports -
Materials, Design and Manufacture
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 13
(2002) Installation of Sprinkler Systems
NFPA 24
(2002) Installation of Private Fire
Service Mains and Their Appurtenances
NFPA 70
(2005) National Electrical Code
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Paint 25
(1997; R 2000) Zinc Oxide, Alkyd, Linseed
Oil Primer for Use Over Hand Cleaned
Steel, Type I and Type II
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS TT-E-489
(Rev J; Notice 1)) Enamel, Alkyd, Gloss,
Low Voc Content
FS TT-P-664
(Rev D) Primer Coating, Alkyd,
Free, VOC-Compliant
UNDERWRITERS LABORATORIES (UL)
UL 262
Service
UL 789
(2004) Indicator Posts for Fire-Protection
Service
UL Fire Prot Dir
(2004) Fire Protection Equipment Directory
1.2
SYSTEM DESCRIPTION
Design [and provide] [new] [and] [modify existing] automatic dry pipe fire
extinguishing sprinkler systems for complete fire protection coverage
throughout [_____].
1.3
SPRINKLER SYSTEM DESIGN
**************************************************************************
NOTE: Use hydraulic calculations for all new
systems over 93 sq. m 1000 sq ft. Use hydraulic
calculations or pipe schedules for new installations
less than 93 sq. m 1000 sq ft, and for additions to
existing pipe schedule systems. When hydraulic
calculations are not included, delete paragraphs
entitled "Water Distribution," "Density of
Application of Water," "Sprinkler Discharge Area,"
"Outside Hose Allowance," "Friction Losses," and
"Water Supply." Earthquake protection is required
SECTION 13935N