a fire alarm system riser diagram indicating
circuits and risers.
**************************************************************************
This work includes designing and providing [a new, complete,] [and]
[modifying the existing] analog/addressable fire alarm system as described
herein and on the contract drawings for the [Building name]. The system
shall include wiring, raceways, pull boxes, terminal cabinets, outlet and
mounting boxes, control equipment, alarm, and supervisory signal initiating
devices, alarm notification appliances, supervising station fire alarm
system transmitter, and other accessories and miscellaneous items required
for a complete operating system even though each item is not specifically
mentioned or described. Provide system[s] complete and ready for
operation. Equipment, materials, installation, workmanship, inspection, and
testing shall be in strict accordance with the required and advisory
provisions of NFPA 72 [and] [_____] except as modified herein. [The system
layout on the drawings show the intent of coverage and are shown in
suggested locations. Final quantity, layout, and coordination is the
responsibility of the Contractor.] [A single fire alarm control panel is
indicated with terminal cabinets at each floor at each riser location.
Where remote fire alarm control units are needed, they shall be provided at
a terminal cabinet location.] Each remote fire alarm control unit shall be
powered from a wiring riser specifically for that use or from a local
emergency power panel located on the same floor as the remote fire alarm
notification appliances may be located in the remote fire alarm control
units.
1.4
SUBMITTALS
**************************************************************************
NOTE: Submittals must be limited to those necessary
for adequate quality control. The importance of an
item in the project should be one of the primary
factors in determining if a submittal for the item
should be required.
A "G" following a submittal item indicates that the
submittal requires Government approval. Some
submittals are already marked with a "G". Only
delete an existing "G" if the submittal item is not
complex and can be reviewed through the Contractor's
submittal is sufficiently important or complex in
context of the project.
For submittals requiring Government approval on Army
projects, a code of up to three characters within
the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
SECTION 13855N
Page 6