1.10
QUALITY ASSURANCE
1.10.1
Qualifications of Installer
Ensure that the installer is UL certified for the installation and testing
of the fire alarm systems. Furnish proof of this listing. A list of
installer's personnel shall be furnished as part of the submittals package.
1.10.2
Manufacturer's Technical Representative
Provide the services of a qualified manufacturer's technical representative
or technician, experienced in the installation and operation of the type of
system being provided to supervise the installation, adjustment,
preliminary testing and final testing of the system and to provide
instruction to Government maintenance and operating personnel
1.10.3
Qualification of System Technician
Installation drawings, shop drawings and as-built drawings shall be
prepared by, or under the supervision of, a qualified technician.
Qualified technician shall be an individual who is experienced with the
types of work specified herein, and is currently certified by the National
Institute for Certification in Engineering Technologies (NICET) as an
engineering technician with minimum Level-III certification in fire alarm
system program. Contractor shall submit data showing the names and
certification of the technician as specified in the paragraph entitled
"Submittals".
PART 2
PRODUCTS
2.1
**************************************************************************
NOTE: OPNAV INSTRUCTION 2410.11H requires that
funds shall not be obligated for the procurement of
has been obtained. As soon as possible, but no
later than Schematic Design, the designer shall
to ensure that the using activity submits a DD Form
1494, APPLICATION FOR FREQUENCY ALLOCATION, for a
Stage 1 ("Conceptual Development") allocation (See
DD Form 1494 Preparation Guide). Stage 1 allocation
authority (i.e. approval) must be obtained prior to
advertisement of the contract.
In order to avoid potential contract delays, the
frequency assignment should be included in the
specification when possible. In some cases it may
be necessary or desirable for the designer to
perform a frequency intermodulation analyses or set
up radio monitoring and recording equipment on the
proposed frequency to verify that the frequency is
For additional information, contact the facility
SECTION 13853N