furnishings, drawn in 1:50 or larger scale.
1.5.2
Wiring Diagrams
Submit wiring diagrams for the complete system showing points of connection
and terminals to be used for each field connection. Show wire color
coding, wire counts, and end-of line-supervisory devices.
1.5.3
Mounting Details
Submit details of each type of transmitter mounting including antenna
mounting detail.
1.6
ALARM SYSTEM POWER CALCULATIONS
Submit design calculations to substantiate that the battery capacity
transmitters[ and interface units] and for receiving, decoding and control
equipment.
1.7
FIRE ALARM SYSTEM UL OR FM LISTING
Submit copies of current UL Fire Prot Dir listings or FM P7825 approvals
for all equipment furnished. Submit UL listing or FM approval for
transmitters, interface equipment, and receiving/control equipment showing
that such equipment is listed or approved for use together as an integrated
system.
1.8
QUALIFICATIONS
1.8.1
List of Prior Installations
Prior to commencing work, submit data showing that the Contractor has
successfully installed radio fire reporting systems, or that he has a firm
contractual agreement with a subcontractor having such required experience.
The data shall include the names and locations of at least two
installations where the Contractor, or the subcontractor referred to above,
has installed such systems. Indicate the type and design of these systems
and provide written certification from the users that these systems have
performed satisfactorily in the manner intended for a period of not less
than 18 months.
1.8.2
Manufacturer's Technical Representative
Submit names of the manufacturer's technical representative(s) who will
supervise installation and testing of the system, and who will provide
instruction to government personnel, along with the manufacturer's
certification of the qualifications of the named representative(s).
1.9
SYSTEM AS-BUILT DRAWINGS
Upon completion, furnish to the Contracting Officer one complete set of
reproducible as-built drawings and five copy sets, including system layout
mm 34 by 22 inches, drawn to the same scale as the contract drawings, with
title block similar to the contract drawings. Reproducible drawings shall
be on mylar film. Furnish as-built drawings in addition to the record
drawings required by Division 01.
SECTION 13853N
Page 12