one common normally open (closes on alarm) dry alarm
contact available for use. If it is desired to
transmit protected premises supervisory and/or
trouble signals, then the control unit requires
additional common trouble or supervisory output dry
contacts. In cases where it may be desirable to
transmit distinct alarm signals per zone, or per
group of initiating devices, the control unit will
need individual zone output dry alarm contacts or
programmable output dry contacts. In some cases it
may be necessary to modify existing control units
by installing additional output modules supplied by
the manufacturer of the control unit. If
modification of existing control units is not
possible due to non-availability of the necessary
modules or lack of space within the panel,
replacement with new control units in order to
provide the necessary dry alarm contacts will be
required. For installation of new control units for
conventional systems, include Section 13852,
"Interior Fire Detection and Alarm System." For
installation of new control units for addressable
systems, include Section 13855, "Analog Addressable
Interior Fire Detection and Alarm System". For
additional guidance, consult the NAVFAC EFD/EFA Fire
Protection Engineer having jurisdiction.
**************************************************************************
Provide a complete and useable standard system, complying with NFPA 70,
NFPA 72, and this specification Provide system connections to protected
premises fire alarm system [and fire suppression/extinguishing system]
control units[ ,and dry contact initiating devices] as shown in accordance
with NFPA 72.[ New protected premises fire alarm systems are specified in
Section 13852N INTERIOR FIRE DETECTION AND ALARM SYSTEM] [and][ Section
13855N ANALOG ADDRESSABLE INTERIOR FIRE DETECTION AND ALARM SYSTEM].
Provide system with[ manual alarm ("street") boxes][ and][ master boxes]
as defined in NFPA 72 where shown, to allow manual initiation of fire[ and
emergency medical][ and police response] alarm transmissions. System shall
be permitted to use one-way or two-way (interrogation) communication, or
both, to comply with the performance requirements specified herein. If a
two-way system is provided, the term "transmitter" as used in this section
1.4
SUBMITTALS
**************************************************************************
NOTE: Submittals must be limited to those necessary
for adequate quality control. The importance of an
item in the project should be one of the primary
factors in determining if a submittal for the item
should be required.
A "G" following a submittal item indicates that the
submittal requires Government approval. Some
submittals are already marked with a "G". Only
delete an existing "G" if the submittal item is not
complex and can be reviewed through the Contractor's
SECTION 13853N
Page 9