2.1.8
System Printer
The system printer shall consist of main control unit, printer section,
alarm monitor section, and auxiliary unit with power supply and auxiliary
components. The total unit shall contain electronic circuitry and
connections and input circuit devices to receive and log by time and date
starting and completion of the watchtour system. The total unit shall be
desk mounted in a rack type desk enclosure. Unit shall be for operation on
120 V ac. Provide auxiliary contact for additional printing out of fire
detection system alarms.
2.1.8.1
Printer Speed and Output
Printer shall be medium speed, three lines per second, roll type with take
up device for 216 mm 8 1/2 inch roll paper. Unit shall contain controls
for manual and automatic printout.
2.1.8.2
Printer Clock
Clock shall provide time log data for month, day, hour, and minute. Clock
shall also alarm at designated time to remind control of tour start. If
tour start has been activated, alarm shall not sound. Devices for setting
and adjusting time controls shall be behind a locked panel. Time shall be
adjustable from 0 to 60 minutes. Unit shall contain display for time and
date.
2.1.8.3
Printer Input
Input devices shall provide alpha-numeric print-out for each watchtour
system from relay contact closure indicated on system wiring diagram.
Auxiliary devices shall be provided to interconnect into individual
watchtour wiring systems.
2.1.8.4
Front control panel shall contain power on switch and pilot lamp and manual
print-out switch.
2.2
WIRE AND CONDUIT
Wire and conduit shall conform to UL 6 and UL 797.
Cabinets and boxes
shall conform to UL 50.
2.2.1
Power Wiring
Provide power wiring, conduit, and outlet boxes for the watchtour system as
specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM.
2.2.2
Control Circuit Wiring
Provide control circuits in accordance with Section 16402 INTERIOR
DISTRIBUTION SYSTEM. Wire and number of conductors as recommended by the
watchtour system manufacturer.
SECTION 13799
Page 8