Submit for the overall system to include the watchtour station,
watchtour panel, and start station, auxiliary relay, control power
transformer, wire and conduit. Indicate how each item of
equipment will function in the system and include an overall
system schematic indicating relationships of watchtour system
devices on one line diagram.
SD-03 Product Data
Watchtour system components
Submit for materials and equipment to be incorporated in work.
SD-07 Certificates
Watchtour system components
SD-10 Operation and Maintenance Data
Watchtour system, Data Package 2
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
1.4
QUALITY ASSURANCE
The watchtour system shall be an integrated design of a single supplier.
1.4.1
Watchtour system
Submit, attesting that materials meet specified requirements.
PART 2
PRODUCTS
2.1
WATCHTOUR SYSTEM EQUIPMENT
Equipment and components of watchtour systems shall conform to applicable
requirements of Article 810, NFPA 70.
2.1.1
Watchtour Station
The watchtour station shall be recessed mounted with face plate mounted
flush on wall 1830 mm 6 feet above the area finished floor. Round key
operators shall be spring return keyswitch with key removable only in off
position, momentary contact, normally open-rated at 10 amperes, 120 V ac.
Device plate shall be brown nylon attached to outlet box with nonremovable
fasteners.
2.1.2
Watchtour Panels
Provide panel for the watchtour system controls.
Watchtour panel shall be
custom built for the specific area.
2.1.2.1
Fabrication
**************************************************************************
NOTE: Insure maximum dimensions required are shown
on the drawing.
SECTION 13799
Page 6