suitable for the warm storage of blankets in the second compartment.
2.14.1
Fabrication
Cabinet shall be welded or riveted, with a stainless steel interior and
manufacturer's standard factory finished exterior.
2.14.2
Heated Compartment
Each heated compartment shall be capable of selectively maintaining the
solutions environment in a range of 37 to 72 degrees C 97 to 160 degrees F
plus or minus 5 degrees C 10 degrees F of set temperature. Heated
compartment shall be fully insulated with an R-value of 3.5 or greater.
temperature uniformity.
2.14.3
Controls
Controls shall include indicator lights to signify various phases of
operation. An over temperature control shall be incorporated that will
shut off heat source, actuate an audible alarm and a visual signal when
temperature inside the cabinet exceeds set point by 8 degrees C 15 degrees F.
Electric unit shall be: 120/208/240 volt, single phase, 2000 watts.
2.14.4
Two Compartment Units
Where two compartment units are scheduled, both compartments shall be
heated, have independent controls, and include adjustable corrosion
resistant shelves.
2.15
BEDPAN WASHER-SANITIZER
Bedpan washer-sanitizer shall be a built-in device for the hands-free
rinsing and sanitizing of heat-resistant hospital bedpans and urinals,
utilizing water and steam from building source.
2.15.1
General
Unit shall be type as scheduled, and be able to sanitize a standard adult
size bedpan or a male urinal each cycle. Automatic control shall provide
for a cold water flush and rinse, followed by a steam sanitizing phase with
a signal light to indicate cycle is in progress.
2.15.2
Door
Door shall incorporate an air intake slot and be flanged to prevent leakage
of water or excess steam. When foot pedal control is depressed, door shall
open while simultaneously releasing utensil holding members, and door shall
close automatically when foot pedal control is released.
2.16
Exposed carbon steel surfaces of equipment shall be protected by
manufacturer's standard finish. Unless otherwise specified, exposed
stainless steel surfaces of all equipment shall have satin No. 3 or No. 4
finish unless otherwise approved.
SECTION 11710
Page 26