e. Surgical Instruments, at least 15 kg 32 pounds, including
retractors, forceps, and hemostats.
2.13
WATER DISTILLATION EQUIPMENT
2.13.1
Laboratory Distilling Apparatus
Laboratory distilling apparatus shall produce distillate free of pyrogen
and containing not more than 1.0 ppm total solids, with a pH value of 5.4
to 7.2, an electrical resistance of not less than 300,000 ohms per
centimeter (ohms/cm) at 25 degrees C 77 degrees F. Distilling apparatus
shall be passivated stainless steel, tin-coated copper or tin-coated copper
alloy, or titanium. Parts of copper or copper alloy in contact with water
vapor and distillate shall be coated with tin 0.025 mm 0.001 inch thick,
minimum. Valves, tubing, and fittings shall be passivated stainless steel,
tin-lined copper, or tin-lined copper alloy. Exterior surfaces of copper
shall be polished nickel or chromium plate. Tin lining in piping, tubing,
valves, or fittings shall be 1.6 mm 1/16 inch thick, minimum. Distillate
collector, still body, and condenser shall be stainless steel. Metallic
surfaces in contact with distillate shall not contaminate the distillate.
2.13.1.1
A meter shall monitor water quality and include an automatic diverter
device to discharge effluent to waste if the effluent is not of acceptable
purity. The meter shall be the electronic indicating and recording type
operating on 120-volt, single-phase, 60 Hz current. Meter shall be
suitable for wall mounting. Solid-state electronic circuitry will be
acceptable. Indicator shall be a horizontal scale approximately 150 mm 6
inches long with easily read graduations and a prominent mark at the point
of minimum quality. Recorder shall be 30-day strip chart type which prints
by a stylus against pressure-sensitive paper. Conductivity cell electrodes
and automatic temperature compensating thermistor shall be contained within
a glass or titanium body secured between the adapter and draw-off cock to
register and record the quality of the distillate at the outlet of the
still at all times. Meter shall have a cam switch to actuate a solenoid
valve which will divert water with less than 300,000 ohms/cm resistance to
waste automatically. An alarm shall sound when water is discharged to
waste. The alarm shall be provided with a manual shut-off. One year's
supply of pressure-sensitive strip chart paper shall be provided.
2.13.1.2
Additional Equipment
Additional equipment shall include thermostatic steam trap, check valve,
2.13.1.3
Disassembly
Major components of the still, including the condenser, shall be easily
disassembled and reassembled for cleaning and maintenance.
2.13.1.4
Mounting Devices
All parts of mounting bracket devices, including bolts and screws for
securing brackets to wall, shall be stainless steel or welded steel with a
corrosive resistant finish.
SECTION 11710