terminals) shall be provided in panels to terminate field and
interconnection wiring.
2.2.4.2
Control System
Control power transformers, relays, adjustable timers, auxiliary contacts,
switches, or additional equipment as required shall be provided to
interconnect the filter equipment to a remote plant monitoring system, and
drawings. Conduit wiring between control panels and control devices shall
be furnished as part of this specification. The Contractor shall submit a
description of the control system including, but not be limited to, the
following items:
a.
Product information for sensors/transducers and field instruments.
b.
Programmable Controller System Information
(1)
System Description
(2)
Hardware Description
(3)
Software Description
c.
Panels, Consoles, and Cabinets Information
(1)
Layout Drawings
(2) Panel schematic and internal point-to-point wiring
interconnect and/or piping diagrams
(3) Electrical control schematics in accordance with JIC
standards for all circuits indicated in the specifications or on
acceptable and no tables or charts to describe wire numbers will
be acceptable. Wires shall be labeled and shown on the submittal
drawings.
(4)
Plan showing equipment layout.
(5) Stock lists or Bill of Materials for each panel including
tag number, functional name, manufacturer's name, manufacturer's
model number, and quantity for components mounted in and on the
panel, console, or cabinet.
stations, lighting panels, and motor starters.
e. Instrument loop diagrams for analog display, control and I/O loops
prepared using ISA standard symbols.
f. System Software Documentation shall include the following as a
minimum:
(1)
Complete hard copies of ladder diagram programming.
(2) Complete listing of external and internal I/O address
assignments, register assignments, and preset constant values
SECTION 11393