Handrailing
Waste oil transfer pump
Oily waste transfer pump
Sludge transfer pump
Sludge or waste oil storage tanks
Immersion heaters
Tank windows
oil content monitor, oil-water interface sensors,
oil flooded alarms, tank level indicators)
Inlet strainer (duplex)
Air vent valve
Pitot tube sampling valve assemblies
Check valves
Manually actuated valves
Motor actuated valves
Explosion proof doors
Separator backwash system
Select and specify as required. For those
accessories required in the project, specify
detailed requirements (including sizes, ratings,
capacities, performance characteristics) in
subparagraphs under paragraph entitled "ACCESSORIES
[AND ACCESSORY EQUIPMENT]."
Where the separator is to be mounted in a concrete
vault with a hatch cover, the designer shall
address, as a minimum, the following:
1. Hatch covers shall provide access to the entire
separator.
2.
Hatch covers shall lock in the open position.
3.
Light weight covers for non-traffic areas.
4. Interior ladder rungs shall not be set away from
cover opening so as to require a person to swing in
and grab.
**************************************************************************
**************************************************************************
NOTE: Review applicable Federal, State, and local
air pollution and ventilation requirements to
determine need for vapor containment.
**************************************************************************
Provide shop fabricated, skid mounted oil-water separator, or other shop
fabricated unit approved by the Contracting Officer, which is comprised of
a separator containing an inlet compartment, parallel plate [or vertical
tube] oil coalescing compartment, outlet compartment [and the following
accessories]:
[Separator Cover [with vapor proof seal]]
[_____]
SECTION 11311
Page 17