designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Firestopping Materials.
typical details conforming to UL Fire Resist Dir or other details
certified by another nationally recognized testing laboratory,
assembly in lieu of fire-test data or report. For those firestop
applications for which no UL tested system is available through a
manufacturer, a manufacturer's engineering judgement, derived from
similar UL system designs or other tests, shall be submitted for
review and approval prior to installation. Submittal shall
indicate the firestopping material to be provided for each type of
application. When more than a total of 5 penetrations and/or
construction joints are to receive firestopping, provide drawings
that indicate location, "F" and "T" ratings, and type of
application.
SD-07 Certificates
Firestopping Materials.
Certificates attesting that firestopping material complies with
the specified requirements. In lieu of certificates, drawings
be provided. Drawings showing evidence of testing by an alternate
nationally recognized independent laboratory may be substituted.
Installer Qualifications.
Documentation of training and experience.
Inspection.
Manufacturer's representative certification stating that
SECTION 07840
Page 4