SD-09 Manufacturer's Field Reports
Daily Log;G, [_____]
Submit at completion of each day's work. Log shall include a
record of each day's wet bulb and dry bulb temperature readings,
substrate temperature readings, humidity readings, wind speed, and
time of readings, wet film thickness measurements and their
location, and quality control inspection observations. Slit and
core sample information shall be a part of the daily log. Mark
area foamed and locate slit and core samples on roof plan and
submit with daily log.
SD-11 Closeout Submittals
Warranty; G, [_____]
Information Card; G, [_____]
1.4
QUALITY ASSURANCE
1.4.1
Qualification of Manufacturer
**************************************************************************
NOTE: Specify 10 years manufacturer experience
unless directed otherwise by the Government.
**************************************************************************
Sprayed polyurethane foam and elastomeric coating products manufacturer
shall have a minimum of [10][_____] years experience in the manufacture of
polyurethane foam and elastomeric coating products.
[1.4.1.1
Manufacturer's Technical Representative
**************************************************************************
NOTE: Include this paragraph where manufacturer
inspection is required.
**************************************************************************
Manufacturer's technical representative shall have a minimum of 10 years
experience with sprayed polyurethane roof systems products and
installations and be thoroughly familiar with the products to be installed,
installation requirements and practices, quality control of the
installation, and with any special considerations in the geographical area
and climate where construction will take place. The representative shall
be available to perform field inspections and attend meetings as specified.
]1.4.2
Qualification of Applicator
**************************************************************************
NOTE: Specify 5 years as an approved contractor
unless directed otherwise by the Government.
**************************************************************************
The roof system applicator shall have prior manufacturer training in the
application of sprayed polyurethane foam and coating materials. Applicator
shall be certified and approved by the foam and coating manufacturer to
apply the specified materials and provide the specified manufacturer
warranty. Applicator shall have a minimum of [5][_____] years experience