rating shall be shown on the label or provided in a letter of
certification.
Gaskets and Insulating Compounds
Two samples of each type to be used and descriptive data.
Sealant
One sample, approximately 0.5 kg 1 pound, and descriptive data.
Concealed Anchor Clips
Two samples of each type used.
Subpurlins
One piece, 225 mm 9 inches long.
EPDM Rubber Boots
One piece of each type.
SD-06 Test Reports
The report shall include the following information:
a. Details of the SSSMR system showing the roof panel
cross-section with dimensions and thickness.
b.
Details of the anchor clip, dimensions, and thickness.
c. Type of fasteners, size, and the number required for each
connection.
d.
Purlins/subpurlins size and spacing used in the test.
e.
Description of the seaming operation including equipment
used.
f. Maximum allowable uplift pressures. These pressures are
determined from the ultimate load divided by a factor of safety
equal to 1.65.
g. Any additional information required to identify the SSSMR
system tested.
h. Signature and seal of an independent registered engineer
who witnessed the test.
SD-07 Certificates
Structural Standing Seam Metal Roof
a. Certification that the actual thickness of uncoated
sheets used in SSSMRS components including roofing panels,
subpurlins, and concealed anchor clips complies with specified
SECTION 07416A
Page 8