be mechanically fastened. Check individual
manufacturer requirement prior to application.
**************************************************************************
[e.
Polystyrene Board:
Shall be in accordance with ASTM C 578, Type
II, IV, or X.]
**************************************************************************
NOTE: Specify high density type wood fiberboard
where the board is used as an overlayment and
fully-adhered single-ply roofing is specified.
**************************************************************************
**************************************************************************
NOTE: Grade 1 insulating board is primarily for use
under built-up roof systems. Grade 2 board is
primarily for use under single-ply roof systems.
**************************************************************************
[f.
Wood Fiberboard: ASTM C 208[, high density], except 4 by 4 feet
maximum board size.
ASTM C 208 Type II, Grade 1 or 2, roof insulating board, treated with
sizing, wax or bituminous impregnation. Bituminous impregnation shall be
limited to 4 percent by weight when used over steel decks. Maximum board
size: 4 feet by 4 feet.]
2.1.2
Mineral-Fiber Insulation Board
ASTM C 726.
2.1.3
Recovered Materials
extent practical. The required minimum recycled material content for the
listed materials are:
23
percent
postconsumer paper
Polyisocyanurate/polyurethane:
9
percent
recovered material
Phenolic Rigid Foam:
5
percent
recovered material
Wood Fiberboard
[ ]
percent
recovered material
**************************************************************************
NOTE: Whenever possible, provide insulation which
has a minimum of 4 percent post consumer waste or 20
percent recycled material by weight of installed
products as defined by (NIBS) September 1999.
**************************************************************************
2.1.4
Insulation Thickness
As necessary to provide a thermal resistance (R value) of [_____] or more
[for average thickness of tapered system]. Thickness shall be based on the
"R" value for aged insulation. [Insulation over steel decks shall satisfy
both specified R value and minimum thickness for width of rib opening
recommended in insulation manufacturer's published literature].
SECTION 07220
Page 13