1.3
SUBMITTALS
**************************************************************************
NOTE: Submittals must be limited to those necessary
for adequate quality control. The importance of an
item in the project should be one of the primary
factors in determining if a submittal for the item
should be required.
A "G" following a submittal item indicates that the
submittal requires Government approval. Some
submittals are already marked with a "G". Only
delete an existing "G" if the submittal item is not
complex and can be reviewed through the Contractor's
submittal is sufficiently important or complex in
context of the project.
For submittals requiring Government approval on Army
projects, a code of up to three characters within
the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-03 Product Data
Concrete Mixture Proportioning[; G][; G, [_____]]
Concrete mixture proportions shall be determined by the
Contractor and submitted for review. The concrete mixture
quantities of all ingredients per cubic meter yard and nominal
maximum coarse aggregate size that will be used in the manufacture
of each quality of concrete shall be stated. Proportions shall
indicate the mass of cement, pozzolan and ground granulated
blast-furnace (GGBF) slag when used, and water; the mass of
aggregates in a saturated surface-dry condition; and the
quantities of admixtures. The submission shall be accompanied by
test reports from a laboratory complying with ASTM C 1077 which
SECTION 03301A
Page 11