inside diameter.
Where sulfate-resistant pipe is required and
Type V cement. Specify Type II (moderate sulfate
resisting) cement when water-soluble sulfates (as
S04) in the soil are in the range of 0.1 to 0.2
percent and, for water, are in the range of 150 to
resisting) cement when soils contain in excess of
0.2 percent water-soluble sulfate and water samples
areas where reactive aggregates are known to occur,
specify low alkali cement.
The following are requirements for LANTNAVFACENGCOM
projects: Pipe sizes under 300 mm (12 inch)
sizes 300 mm (12 inch) diameter through 600 mm (24
inch) diameter may be either reinforced or
nonreinforced concrete pipe. Pipe sizes larger than
600 mm (24 inch) diameter shall be reinforced
concrete pipe.
**************************************************************************
ASTM C 76M ASTM C 76, Class [I] [II] [III] [IV] [V], or ASTM C 655, [_____]
D-Load.
2.1.1.1
Reinforced Arch Culvert and Storm Drainpipe
ASTM C 506M ASTM C 506, Class [A-II] [A-III] [A-IV].
2.1.1.2
Reinforced Elliptical Culvert and Storm Drainpipe
ASTM C 507M ASTM C 507. Horizontal elliptical pipe shall be Class [HE-A]
[HE-I] [HE-II] [HE-III] [HE-IV]. Vertical elliptical pipe shall be Class
[VE-II] [VE-III] [VE-IV] [VE-V] [VE-VI].
2.1.1.3
Nonreinforced Pipe
ASTM C 14M ASTM C 14, Class [1] [2] [3].
2.1.1.4
Cast-In-Place Nonreinforced Conduit
**************************************************************************
NOTE: This type conduit should not be used beneath
structures, for drain crossings, adjacent to paved
areas, or under high fills.
**************************************************************************
ACI 346, except that testing shall be the responsibility of and at the
expense of the Contractor. In the case of other conflicts between ACI 346
2.1.2
Clay Pipe
**************************************************************************
NOTE: Specify "bell-and-spigot piping only" in
areas where corrosion problems may be anticipated
SECTION 02630
Page 15