1.7
EXISTING CONDITIONS
Submit drawings of existing conditions, after
a thorough inspection of the
area by the Contractor in the presence of the
Contracting Officer. Details
the site and adjacent areas.
Submit copies of the records for verification
before starting work.
1.8
INSTALLER QUALIFICATIONS
Install specified materials by a licensed undergroun utility contractor
licensed for such work in the state where the work is to be performed.
Installing Contractor's License shall be current and be state certified or
state registered.
PART 2
PRODUCTS
2.1
PIPELINE MATERIALS
Pipe shall conform to the respective specifications and other requirements
specified below.
2.1.1
Cast-Iron Soil Piping
2.1.1.1
Cast-Iron Hub and Spigot Soil Pipe and Fittings
ASTM A 74, [service] [extra heavy], with ASTM C 564 compression-type rubber
gaskets.
2.1.1.2
Cast-Iron Hubless Soil Pipe and Fittings
**************************************************************************
NOTE: Delete this paragraph for areas where hubless
fittings are considered inappropriate due to failure
of coupling by corrosion.
**************************************************************************
CISPI 301 with CISPI 310 coupling joints.
2.1.2
Clay Piping
2.1.2.1
Clay Pipe and Fittings
**************************************************************************
NOTE: Tables of trench loadings, trench backfill
loads, and supporting strengths of clay pipe are
included in the Clay Pipe Engineering Manual (1982
edition) of the National Clay Pipe Institute. The
required strength of clay pipe can be derived from
these tables when depth of trench is known.
Specify "bell-and-spigot piping only" in areas where
corrosion problems may be anticipated with the
stainless steel parts of the couplings used for
plain-end piping.
**************************************************************************
ASTM C 700, [standard strength] [extra strength] [bell-and-spigot piping
only].
SECTION 02531
Page 17